A NEW TECHNIQUE FOR TRANSIENT RECOVERY VOLTAGE SUPPRESSION ON GENERATOR CIRCUIT BREAKER FOR GENERATOR FED FAULTS
• 2013
Publication Information
Authors
M. A. ABD-ALLA Ebrahim A. BADRAN Abdelsalam H. HAMZA Tamer ELYAN
Keywords
Not Available
Journal
Not Available
Publisher
Not Available
Volume
Not Available
Issue
Not Available
Pages
Not Available
publication.type
International
Paper Link
Not Available
Supplementary Materials
Not Available
Abstract
In this paper, the generator circuit breaker (GenCB) is simulated using ATP- EMTP software package. Four main stages of the breaker’s operating processes are considered, namely; the closed contacts stage, the arc burning stage, the arc extinguishing stage and the opened contacts stage. Therefore, not only the dynamic conductance during current zero are considered but also the effects of arc voltage on the arcing times are included. The simulation is tested in a representative network and the results are compared with IEEE Generator Circuit Breaker standards. A new mitigation technique is introduced to reduce the transient recovery voltage and the rate of rise of re-striking voltage during switching period. The results show that the new technique reduces both the TRV and RRRV effectively with respect to previous ones.