A NEW TECHNIQUE FOR TRANSIENT RECOVERY VOLTAGE SUPPRESSION ON GENERATOR CIRCUIT BREAKER FOR GENERATOR FED FAULTS
• 2013
معلومات البحث
المؤلفون
M. A. ABD-ALLA Ebrahim A. BADRAN Abdelsalam H. HAMZA Tamer ELYAN
الكلمات المفتاحية
Not Available
المجلة العلمية
Not Available
الناشر
Not Available
المجلد
Not Available
العدد
Not Available
الصفحات
Not Available
publication.type
International
رابط البحث
Not Available
المواد المرفقة
Not Available
الملخص
In this paper, the generator circuit breaker (GenCB) is simulated using ATP- EMTP software package. Four main stages of the breaker’s operating processes are considered, namely; the closed contacts stage, the arc burning stage, the arc extinguishing stage and the opened contacts stage. Therefore, not only the dynamic conductance during current zero are considered but also the effects of arc voltage on the arcing times are included. The simulation is tested in a representative network and the results are compared with IEEE Generator Circuit Breaker standards. A new mitigation technique is introduced to reduce the transient recovery voltage and the rate of rise of re-striking voltage during switching period. The results show that the new technique reduces both the TRV and RRRV effectively with respect to previous ones.