| publication name | Cyclic Loading of Underground Cables Including the Variations of Backfill Soil Thermal Resistivity and Specific Heat with Temperature Variation |
|---|---|
| Authors | Ossama El-Sayied Gouda, Gomaa Fahmey A Osman, Waleed AA Salem, Shawky H Arafa |
| year | 2018 |
| keywords | |
| journal | IEEE Transactions on Power Delivery |
| volume | Not Available |
| issue | Not Available |
| pages | Not Available |
| publisher | Not Available |
| Local/International | International |
| Paper Link | Not Available |
| Full paper | download |
| Supplementary materials | Not Available |
Abstract
The aim of this paper is to calculate the temperature distribution of a cable conductor and the soil surrounding the cable under cyclic loading conditions, taking into account the formation of a drying zone in the backfill material. The thermal model of an underground cable is considered by using the IEC 60853-2 method, including the effects of the variations in temperature on the thermal resistivity and specific heat of the soil. The results are compared with IEC 60853-2 and thermoelectric equivalent method calculations. This study is done on eight sandy soil types as backfill materials, and calculations are carried out by using a 33-kVx cable. The results indicate that the modifications done on the IEC 60853-2 method are required to improve its capability to simulate the field conditions during load cycling of power cables.