Banner

Cyclic Loading of Underground Cables Including the Variations of Backfill Soil Thermal Resistivity and Specific Heat with Temperature Variation

IEEE Transactions on Power Delivery • 2018
Back
Publication Information
Authors Ossama El-Sayied Gouda, Gomaa Fahmey A Osman, Waleed AA Salem, Shawky H Arafa
Keywords Not Available
Journal IEEE Transactions on Power Delivery
Publisher Not Available
Volume Not Available
Issue Not Available
Pages Not Available
publication.type International
Paper Link Not Available
Supplementary Materials Not Available
Abstract
The aim of this paper is to calculate the temperature distribution of a cable conductor and the soil surrounding the cable under cyclic loading conditions, taking into account the formation of a drying zone in the backfill material. The thermal model of an underground cable is considered by using the IEC 60853-2 method, including the effects of the variations in temperature on the thermal resistivity and specific heat of the soil. The results are compared with IEC 60853-2 and thermoelectric equivalent method calculations. This study is done on eight sandy soil types as backfill materials, and calculations are carried out by using a 33-kVx cable. The results indicate that the modifications done on the IEC 60853-2 method are required to improve its capability to simulate the field conditions during load cycling of power cables.