Banner

A Study of K Factor Power Transformer Characteristics by Modeling Simulation

• 2011
Back
Publication Information
Authors O.E. Gouda, G.M. Amer, W.A.A. Salem
Keywords Not Available
Journal Not Available
Publisher Not Available
Volume Not Available
Issue Not Available
Pages Not Available
publication.type International
Paper Link Open Link
Supplementary Materials Not Available
Abstract
Harmonic currents generated by nonlinear loads can cause overheating and premature failure in power transformers. K-factor transformers are specially designed to accommodate harmonic currents and offer protection against overheating caused by harmonics. They minimize harmonic current loss and have an additional thermal capacity of known limits. According to IEEE C57-110, the winding eddy current losses are considered proportional to the harmonic current squared times its harmonic number. K-factor is only an indicative value and the authors' main objective in this paper is to study the effect of harmonics on oil filled transformer and to simulate harmonic behavior using Matlab Simulink. A case study is simulated in order to investigate K-factor values with pumping loads, with and without the use of harmonic filters. Results are compared with measured values.