"Three-Phase Voltage-Source UPS Inverters with Voltage-Controlled Current-Regulated Feedback Control Scheme," in Proceedings of the IEEE International conference on Industrial Electronics, Control and Instrumentation (IECON), Bologna, Italy, September 5-9, pp. 497-502.
• 1994
معلومات البحث
المؤلفون
Naser Abdel-Rahim and John Quaicoe
الكلمات المفتاحية
Not Available
المجلة العلمية
Not Available
الناشر
Not Available
المجلد
Not Available
العدد
Not Available
الصفحات
Not Available
publication.type
International
رابط البحث
Open Link
المواد المرفقة
Not Available
الملخص
This paper presents a novel control strategy for three-phase voltage-source UPS inverters with second order L-C filters. The control scheme is based on sensing the current in the filter capacitor and using it in an inner feedback loop. An outer capacitor voltage loop is also incorporated to ensure sinusoidal load voltage. A general model of the power circuit (inverter, filter, and load) is first established. Computer simulation results of the proposed three-phase voltage-source UPS system with an R-L load from “cold” start to full-load is then presented to demonstrate the suitability of the proposed control scheme for UPS applications. The dynamic response of the proposed scheme is investigated using rotating frame of reference and small signal approximation. A control loop regulator is then selected to enhance the dynamic response of the control scheme and achieve the desired performance of the UPS system. It is shown in the paper that the control scheme offers many advantages for UPS applications. It is simple to implement and capable of producing nearly perfect sinusoidal load voltage waveform at moderate switching frequency and reasonable size of filter parameters. The scheme has fast dynamic response and provides high voltage utilization of the DC source. In addition, it provides peak c
أعضاء هيئة التدريس - جامعة بنها