Banner

Experimental Study on the Performance Enhancement of a Water Chiller

Scientific Journal of October 6 University • 2018
Back
Publication Information
Authors M.M. Alkhaja; M.R. Salem; K.M. Elshazly; M.F. Abdrabbo
Keywords Helically coiled tube; Evaporator; Water chiller; Curvature; Torsion; Performance
Journal Scientific Journal of October 6 University
Publisher October 6 University
Volume Not Available
Issue Not Available
Pages Not Available
publication.type Local
Paper Link Not Available
Supplementary Materials Mohamed Reda Aly Abd-Elhamid Salem_Manuscript - 1.pdf
Abstract
This work experimentally investigates the effect of the geometrical parameters of a vertical helically coiled tube in tube (HCTIT) evaporator on the coefficient of performance (COP) of a vapour compression refrigeration system (VCRS) used as a water chiller. Five HCTIT evaporators through which R134a flows in the internal tube, are constructed and tested at different flow rates of the heating water in their annulus. They are geometrically divided into two groups; the first group is fabricated such that the internal tube curvature ratios (δ_(ev,i)) is varied from 0.0238 to 0.0334 while the other group represents another three-different coil torsions (λ) from 0.0522 to 0.0948. The results show that the COP of the VCRS is enhanced with decreasing δ_(ev,i), increasing λ, and increasing the condenser to evaporator pressures ratio. Finally, an experimental correlation is developed to predict the COP of the VCRS.