Algorithm for load cycling correction to minimise the dry zone influences on the cross-linked polyethylene (XLPE) cable insulation
IET Generation, Transmission & Distribution • 2020
Publication Information
Authors
Osama E. Gouda;Gomaa F.A. Osman
Keywords
power cables;algorithm
Journal
IET Generation, Transmission & Distribution
Publisher
IET Generation, Transmission & Distribution
Volume
14
Issue
21
Pages
4684-4693
publication.type
International
Paper Link
Open Link
Supplementary Materials
Not Available
Abstract
Dry zone formation around underground power cables during load cycling may lead to thermal failure of the cable's insulation. This phenomenon has to be recorded to send an alarm to the maintenance crew when the soil around the cable reaches the critical value at which the dry zone has started to be formed. In this study, the buried cable thermal model is modified to include occurrences of dry band formation during dynamic loading. An algorithm has been proposed for corrections of the cable load cycle to maintain the insulation maximum temperature at 85°C and not exceed this limit. This is suggested for reducing the dry zone formation effect on the cable insulation lifetime. The study is done on different single-core cables using different soil samples that can be used as backfill materials. The variations in thermal soil resistivity and soil thermal capacitance with temperature and moisture content of backfill soil are considered. The practical system used for monitoring the dry zone formation around the cable has been proposed.