Banner

A Study of K-Factor Power Transformer Characteristics by Modeling Simulation"ETASR - Engineering, Technology & Applied Science Research"

ETASR - Engineering, Technology & Applied Science Research • 2011
العودة
معلومات البحث
المؤلفون O.Gouda, G. Amer. W. Salem
الكلمات المفتاحية K-factor transformers; harmonics filter; total harmonic distortion
المجلة العلمية ETASR - Engineering, Technology & Applied Science Research
الناشر Not Available
المجلد Vol. 1,N o. 5,
العدد Not Available
الصفحات 114-120
publication.type International
رابط البحث Not Available
المواد المرفقة Not Available
الملخص
Harmonic currents generated by nonlinear loads can
cause overheating and premature failure in power transformers.
K-factor transformers are specially designed to accommodate
harmonic currents and offer protection against overheating
caused by harmonics. They minimize harmonic current loss and
have an additional thermal capacity of known limits. According
to IEEE C57-110, the winding eddy current losses are considered
proportional to the harmonic current squared times its harmonic
number. K-factor is only an indicative value and the authors'
main objective in this paper is to study the effect of harmonics on
oil filled transformer and to simulate harmonic behavior using
Matlab Simulink. A case study is simulated in order to investigate
K-factor values with pumping loads, with and without the use of
harmonic filters. Results are compared with measured values.