Slender reinforced concrete flanged beams: experimental work
Proc Instn Civ. Engrs Structs & Bldgs • 1992
معلومات البحث
المؤلفون
N. K. Subedi,A. Rahem,G. T. Abdel-Rahman.
الكلمات المفتاحية
Not Available
المجلة العلمية
Proc Instn Civ. Engrs Structs & Bldgs
الناشر
Not Available
المجلد
94
العدد
10014
الصفحات
439-468
publication.type
International
رابط البحث
Not Available
المواد المرفقة
Not Available
الملخص
Slender and thin-walled forms of construction are a natural choice for any large-scale structure employing reinforced concrete. Reinforced concrete flanged beams provide structural strength and stability, and their applications range from buildings, offshore structures, flotation units for housing in marshy land to floating hotels. Tests were carried out on a total of 21 reinforced concrete flanged beams, with overall depth web thickness ratios between 40 and 80. The test specimens were mostly large structural elements, some of which measured 2 m x 4 m overall. The web thickness ranged from 20 mm to 33 mm. The test beams represent some of the most slender forms of reinforced concrete construction attempted in a laboratory. Details of beams, method of construction, test procedure, measurements taken and the observed structural behaviour are described. The main modes of failure observed in the test were diagonal splitting, flexural shear and web crushing. The characteristics of the modes of failure and the mechanisms are discussed. The web crushing mode of failure happens suddenly and can be violent.