| publication name | A Proposed Transient Recovery Voltage Mitigation Technique For Generator- Circuit-Breaker Fed Faults |
|---|---|
| Authors | Ebrahim A.Badran, M. A. Abd-Allah, Abdelsalam H.Hamza, Tamer Elyan |
| year | 2013 |
| keywords | GenCB, TRV, RRRV, Fed Faults, ATP-EMTP. |
| journal | Journal of Electrical Systems,J. Electrical Systems 9-1 (2013): 66-72 |
| volume | J. Electrical Systems 9-1 |
| issue | (2013) |
| pages | 66-72 |
| publisher | J. Electrical Systems, Journal of Electrical Systems |
| Local/International | International |
| Paper Link | https://www.researchgate.net/publication/274383040 |
| Full paper | download |
| Supplementary materials | Not Available |
Abstract
In this paper, the generator-circuit-breaker (GenCB) is simulated using ATP-EMTP. The four main stages of the breaker’s operating processes are considered, namely; the closed contacts stage, the arc burning stage, the arc extinguishing stage and the opened contacts stage. Therefore, not only the dynamic conductance during current zero are considered but also the effects of arc voltage on the arcing times are included. The simulation is tested in a representative network and the results are compared with IEEE Generator Circuit Breaker standards. Furthermore, a new mitigation technique is introduced to reduce the transient recovery voltage (TRV) and the rate of rise of re-striking voltage (RRRV) during switching period. The results show that the proposed technique successfully reduces both the TRV and RRRV.