Solutions of thermal management problems for terminal racks of in-row cooling architectures in data centers
Building and Environment • 2021
Publication Information
Authors
S.A. Nada; A.M. Abbas
Keywords
Data centers
In-row cooling
Thermal performance
Top and side containments
Terminal racks
Journal
Building and Environment
Publisher
ELSEVIER
Volume
201
Issue
Not Available
Pages
Not Available
publication.type
International
Paper Link
Open Link
Supplementary Materials
Not Available
Abstract
Problems of hot air recirculation, hot spots, and bad performance indices of data centers at terminal racks were
noticed and reported in the literature. The present work investigates the possible management solutions of
heterogeneous thermal problems for terminal racks in data centers in case of using in-row cooling racks arrays.
Three possible solutions, namely using top aisle containments, top and side aisles containments, and air conditioning unit at the start and end of each rack row, are investigated. Computational Fluid Dynamics(CFD) using
ANSYS-Icepak software as a specialized software in cooling electronic devices is used to conduct this study. A
prototype of a small-scale data center module is experimentally constructed and tested to validate the present
CFD work. Supply Heat Index (SHI), Index of Mixing (IOM), Beta Index (β) and Energy Utilization Index (ηr) are
utilized to investigate, assess and compare the different suggested solutions. The results show that (i) problems of
hot air recirculation, hot spots, and bad performances indices are noticed for the terminal racks if no solution is
applied, (ii) using top aisle containments partially solve the heterogeneous thermal problem of terminal racks,
(iii) using top and sides containments completely solve the problem of hot air recirculation (iv) starting and
ending the racks row with computer air conditioning units solve the problem of the heterogeneous distribution of
intake air temperature along with the racks height and (v) Energy Utilization Coefficient of terminal racks is
increased by 45% if the top and sides containments are applied or starting the racks row with air conditioning
units.
noticed and reported in the literature. The present work investigates the possible management solutions of
heterogeneous thermal problems for terminal racks in data centers in case of using in-row cooling racks arrays.
Three possible solutions, namely using top aisle containments, top and side aisles containments, and air conditioning unit at the start and end of each rack row, are investigated. Computational Fluid Dynamics(CFD) using
ANSYS-Icepak software as a specialized software in cooling electronic devices is used to conduct this study. A
prototype of a small-scale data center module is experimentally constructed and tested to validate the present
CFD work. Supply Heat Index (SHI), Index of Mixing (IOM), Beta Index (β) and Energy Utilization Index (ηr) are
utilized to investigate, assess and compare the different suggested solutions. The results show that (i) problems of
hot air recirculation, hot spots, and bad performances indices are noticed for the terminal racks if no solution is
applied, (ii) using top aisle containments partially solve the heterogeneous thermal problem of terminal racks,
(iii) using top and sides containments completely solve the problem of hot air recirculation (iv) starting and
ending the racks row with computer air conditioning units solve the problem of the heterogeneous distribution of
intake air temperature along with the racks height and (v) Energy Utilization Coefficient of terminal racks is
increased by 45% if the top and sides containments are applied or starting the racks row with air conditioning
units.