Cyclic Loading of Underground Cables Including the Variations of Backfill Soil Thermal Resistivity and Specific Heat With Temperature Variation
IEEE Transactions on Power Delivery • 2018
معلومات البحث
المؤلفون
Ossama El-Sayied Gouda, Gomaa Fahmey A Osman, Waleed AA Salem, Shawky H Arafa
الكلمات المفتاحية
Not Available
المجلة العلمية
IEEE Transactions on Power Delivery
الناشر
IEEE
المجلد
33
العدد
6
الصفحات
3122-3129
publication.type
International
رابط البحث
Not Available
المواد المرفقة
Not Available
الملخص
The aim of this paper is to calculate the temperature distribution of a cable conductor and the soil surrounding the cable under cyclic loading conditions, taking into account the formation of a drying zone in the backfill material. The thermal model of an underground cable is considered by using the IEC 60853-2 method, including the effects of the variations in temperature on the thermal resistivity and specific heat of the soil. The results are compared with IEC 60853-2 and thermoelectric equivalent method calculations. This study is done on eight sandy soil types as backfill materials, and calculations are carried out by using a 33-kVx cable. The results indicate that the modifications done on the IEC 60853-2 method are required to improve its capability to simulate the field conditions during load cycling of power cables.