Banner

2. Experimental parametric study of cooling servers management in data center buildings

• 2017
العودة
معلومات البحث
المؤلفون 21. S.A. Nada, K.E. Elfeky, A.M.A Attia,W.G. Alshaer
الكلمات المفتاحية Data center, experimental physical modeling, cooling management, parametric study
المجلة العلمية Not Available
الناشر Not Available
المجلد Not Available
العدد Not Available
الصفحات Not Available
publication.type International
رابط البحث Not Available
المواد المرفقة Not Available
الملخص
A parametric study of air flow and cooling management of data centers servers is experimentally conducted for different design conditions. A physical scale model of data center accommodating one rack of four servers was designed and constructed for testing purposes. Front and rear rack and server’s temperatures distributions and supply/return heat indices (SHI/RHI) are used to evaluate data center thermal performance. Experiments were conducted to parametrically study the effects of perforated tiles opening ratio, servers power load variation and rack power density. The results showed that (i) perforated tile of 25% opening ratio provides the best results among the other opening ratios, (ii) optimum benefit of cold air in servers cooling is obtained at uniformly power loading of servers (iii) increasing power density decrease air re-circulation but increase air bypass and servers temperature. The present results are compared with previous experimental and CFD results and fair agreement was found.