Banner

Techniques used for Unequally Spaced Grounding Grid Design

Journal of Multidisciplinary Research and Reviews • 2018
العودة
معلومات البحث
المؤلفون Osama Elsayed Gouda, Ghada Mohamed Amer, Omar Mohamed Salim, Eman Amer Elsayed
الكلمات المفتاحية Ground grid, Optimum compression ratio, Particle swarm optimization, Ground potential rise, Step voltage, Touch voltage.
المجلة العلمية Journal of Multidisciplinary Research and Reviews
الناشر Innovation Info Open Access Journals
المجلد 1
العدد 1
الصفحات 1
publication.type Local
رابط البحث Open Link
المواد المرفقة Not Available
الملخص
Grounding system is one of the most important items of the power plants and substation systems design. The main purpose of power system substation grounding grids is to maintain reliable operation and provide protection for personnel and equipment during fault conditions. In any substation planning, economical and effective grounding system plays an essential role since absence of effective grounding grid can result in mal-operation of protective devices and hazardous for operators and substation equipment. Therefore, in this paper, the evolutional technique for unequally spaced grounding grid design is suggested. The design is based on hybridization of optimum compression ratio (OCR) and particle swarm optimization (PSO) techniques. This approach is purposed to control the grounding copper volume of the grounding system with the aid of controlling of unequally spaced grounding conductor lengths with respect to the safety measures. The proposed technique offers almost 20% of copper savings comparing with the optimum compression ratio
method.