Influence of the width and thickness of the flange on the shear capacity of reinforced concrete T- beams.
Al-Azhar University Civil Engineering Research Magazine (CERM) • 2021
معلومات البحث
المؤلفون
Osman M. O. Ramadana;Ahmed H. Abdel-Kareemb; Hala R. Abou safab; and Ibrahim A. El-Azab
الكلمات المفتاحية
Reinforced concrete beam, Flanged beam, shear cracks, Longitudinal reinforcements, Angle of diagonal crack.
المجلة العلمية
Al-Azhar University Civil Engineering Research Magazine (CERM)
الناشر
Not Available
المجلد
43 No. 2
العدد
1110-0990
الصفحات
13
publication.type
Local
رابط البحث
Not Available
المواد المرفقة
Not Available
الملخص
This research presents the test results of experimental study on shear strength of reinforced concrete flanged beams. The test variables in this study were flange dimensions (thickness) and the reinforcement in flange. seven simply supported specimens, consisting of one of them with rectangular cross section and the remaining specimens with T section, subjected to two-point loads were tested until failure. During the test, the values of the diagonal cracks, crack width, strain and the maximum load were observed as well as the deformation of the beams. It was confirmed from the test that the shear capacity of T-beam was higher than for rectangular beams, with the values ranging from 166 to 312%, depending on the flange dimensions and longitudinal reinforcement in flange. In addition, based on the test results, a simple model for predicting the contribution of flange to shear capacity in T-beam was presented and comparison the results.