Heat transfer characteristics and pressure drop of the concentric tube equipped with coiled wires for pulsating turbulent flow
Experimental Thermal and Fluid Science • 2015
معلومات البحث
المؤلفون
Ali A. Abdel Aziz, A.E. Zohi, M.A. Habib
الكلمات المفتاحية
Double-pipe heat exchanger;Coiled wire;Turbulent annulus flow;Pulsated flow
المجلة العلمية
Experimental Thermal and Fluid Science
الناشر
Elsevier Inc.
المجلد
65
العدد
Not Available
الصفحات
41-51
publication.type
International
رابط البحث
Open Link
المواد المرفقة
Not Available
الملخص
The influence of pulsation with different amplitudes on the heat transfer rates in a double-pipe heat exchanger where a coiled wire inserts around the outer surface of the inner tube is investigated. The heat transfer and pressure drop characteristics were investigated for a coiled wire inserts with different pitch values in absence of pulsation. Pulsation frequencies that were produced by using a reciprocating device ranged from 140 to 260 cycles per minute (2.3–4.3 Hz). Five different displacement amplitudes were
used where the stroke length of the reciprocating piston was varied from 60 to 185 mm.
used where the stroke length of the reciprocating piston was varied from 60 to 185 mm.